Home Categories Send inquiry

Electric three way control valve

Three way electric control valve actuator specification

Electric 3-way control valve
Type Method
Electric actuator
  3810L series
  Intelligent integrated type
Usage Regulating
Air supply pressure or Power supply voltage Power: AC 200V±10%  50Hz
Or Power:  AC 380V±10% 50Hz
Connector Normal type:  cable inlet 2-PF(G1/2〞)
Explosive proof:  Protection jacket PF(G3/4〞)
Direct action Input signal increase, stem descend, valve close.
Reaction Input signal increase, stem ascend, valve open.
Input signal Input/output4~20mA.DC
Lag ≤0.8%FS
Linear type ≤+1%FS
Environmental temperature Standard type: -10℃~+60℃
With space heater : -35℃~+60℃
Explosive proof: -10℃~+40℃
Electric 3-way control valve
Accessories
Space heater (normal type)
Non-standard accessories, need special customized notes.

Three way control valve technical parameter

Nominal Diameter DN (mm) 25 32 40 50 65 80 100 125 150 200
Rated Flow Factor (KV) Confluence 8.5 13 21 34 53 85 135 210 340 535
  Distributary 8.5 13 21 34 53 85 135 210 340 535
    Can be Instead by Confluence System          
Rated Stroke L (mm) 16 25 40 60
Diaphragm Active Area Ae (c m 2 ) 280 400 600 1000
Nominal Pressure PN (Mpa) 1.6 4.0 6.4
Inherent Flow Characteristic Straight Line, Parabola
Inherent Adjustable Rate R 30
Working Temperature t( °C ) Common:Cast Iron -20 ~ 200 Cast Steel -40~250 Cast Stainless Steel -60 ~ 250

Heat Dissipation:Cast Steel -40 ~ 450 Cast Stainless Steel -60~450

Two Media Temperature Difference t( °C ) Cast Iron≤ 150 Cast Steel, Cast Stainless Steel≤ 200
Sign Range Pr(kPa) 40~200
Bleed Pressure Ps(MPa) 0.14~0.4
Permit Leakage Rate 10 -4 X Valve Rated Capacity
Permit Pressure Distance  P(MPa) 0.86 0.75 0.48 0.31 0.27 0.18 0.11 0.12 0.09 0.05

 

Three way electric control valve structure

Three way electric control valve flow direction


Electric three way control valve Related Video: